Datasheet

11/12
Tufvassons Transformator AB Märstavägen 20 SE 193 40 Sigtuna Phone +46 (0) 8 594 809 00
Fax +46 (0) 8 592 527 68 E-mail reception@tufvassons.se www.tufvassons.se
A company in the ADDTECH group.
Meets the requirements of the
energy sector
Tufvassons has a wide range of transformers and over fifty years’ experience of
making them ourselves. We offer transformers for environments that set high
requirements on insulation and safety, the energy sector for example. We help you to
make the correct choice, and if you need a product that is not available, we ensure it
is made.
Ideal for
low voltage installations
The transformer is used when there are greater
demands on insulation and safety than normal. It is
suitable for voltage feed in SELV and PELV installations
such as monitoring systems, temperature control,
lighting and alarms. The connection glands are specially
designed to fit tightly round the cable. It goes without
saying that the transformer also has short circuit and
overload protection, and also complies with the
insurance companies' requirement for self-extinguishing
plastic in the housing.
Type: PVS 480
Part. no.: 6024-0195
Input voltage: 230V, 50-60 Hz; (N - L)
Output voltage: 24V
Rated power: 460 VA (19.2A)
Weight: 6 kg
Encapsulation class: IP54
Insulation class: 4.2 kV
Ambient temperature: max 40
o
C (at 50
o
C, the transformer can supply a load of max. 390 VA)
Design: Transformer potted in hard-setting plastic, with grey encapsulation made from impact resistant,
self extinguishing thermoplastics.
- Double insulated (earth connection not required).
- Primary, resettable over-current protection 3.0A.
- Primary terminal 2-pole 4 mm² terminal max torque for the terminal block is 0.5 Nm.
- Secondary terminal 2-pole 16 mm² terminal max torque for the terminal block is 2.0 Nm.
- Entry gland for cable diameter max. 14 mm
Mounting: Wall mounting with 3 screws.
Manufacturing standard: Security EN 61558-1; EN 61558-2-6
Emissions: EN 61 000-6-3; EN 61 000-6-4, IEC 62041
Immunity: EN 61 000-6-1; EN 61 000-6-2, IEC 62041
Other information: If required for the installation in question, the transformer must be connected by an all-pole
switch in permanent installations.