Datasheet
11/11 
Tufvassons Transformator AB  Märstavägen 20  193 40 Sigtuna  Phone +46 (0) 8 594 809 00 
Fax +46 (0) 8 592 527 68  E-mail reception@tufvassons.se  www.tufvassons.se 
A company in the ADDTECH group. 
For lower-energy lighting 
Tufvassons have a wide range of transformers and over fifty years’ experience of 
making them ourselves. We offer safe lighting transformers with low running costs, 
and help you to select the right one. If you need a product that is not available, we 
will ensure it is made.
The transformer that gives lamps 
longer life 
The transformer is suitable for all kinds of low-voltage 
lighting, for 12 VAC for optimum efficiency in the light 
source. The light source will last longest if the 
recommendation for minimum loading is followed. The 
transformer is easy to install (keyhole socket) and to 
connect. The connection clamps are specially designed 
to fit tightly round the cable. And of course, the product 
also has short-circuit and overload protection, and 
complies with the insurance companies' requirement for 
self-extinguishing plastic in the housing. 
Type:  PVS 120 A
Part.no.: 6009-0089
Input voltage:  230V, 50-60 Hz; (N - L)
Output voltage:  11.5V
Lamp power:  max. 120 W (10A), min. 35 W
Weight: 2.2 kg
Encapsulation class:  IP54
Insulation class: 4.2 kV
Ambient temperature:  max 40 
o
C (at 50 
o
C, the transformer can supply a load of max. 100VA)
Design:  - Transformer potted in hard-setting plastic, with grey encapsulation made from impact resistant, 
self extinguishing thermoplastics.
  - Double insulated (earth connection not required). 
  - Primary, resettable over-current protection 0.7A. 
  - Primary clamp connector for cable diameter max. 13 mm, 2-pole 4 mm² terminal.  
  - Secondary clamp connector for cable diameter max. 13 mm, 2-pole 4 mm² terminal. 
  - Max torque for the screw terminal is 0.5 Nm. 
Mounting:  Mounting with 3 screws. The upper 2 holes are keyhole plates.
Manufacturing standard:  Security:  EN 61 558-1; EN 61 558-2-6
  Emissions:  EN 61 000-6-3; EN 61 000-6-4, IEC 62041 
  Immunity:  EN 61 000-6-1; EN 61 000-6-2, IEC 62041 
Other information:  If demanded by the installation regulations, the transformer must be connected by an all-pole 
switch in permanent installations.