12
TERMS:
Cut-out-Temperaturesensedbythe
controllerthatshutsthecompressor
off.
Cut-in-Temperaturesensedbythe
controllerthatturnsthecompressor
on.
REQUIRED TOOLS
• PhillipsHeadScrewdriver
• 5/64"or2mmAllenWrench
• T-7TorxWrench
STE P 1
Unplugthecooler.
STE P 2
Removethescrewsthatsecurethe
temperaturecontroltotheinsetbox.
S T E P 3
Pulloutgentlyfromcabinet.
S T E P 4
Forhighelevationinstallations,it
maybenecessaryto"warm-up"the
setpoints.Tomaketheadjustment,
inserttheappropriatetoolineach
adjustmentscrewandturn1/4ofa
revolutionclockwise(totheright).
Thisprocedurewilladjustboth
thecut-inandcut-outabout2°F
warmer.
S T E P 5
Makesuretoreconnectthepink
wiretotheproperspadeterminal
whenreinstalling.
NOTE:
Mechanical temperature
controllers are affected when
functioning at high altitude. The
cut-in and cut-out
temperatures will be colder than
when the controller functions
closer to sea level
Danfoss Temperature Control (High Altitude Adjustment Only!)
Cut-out Adjustment Screw Allen (5/64"
or 2 mm) (clockwise for warmer)
Cut-in Adjustment Screw Torx (T-7)
(clockwise for warmer)
Compressor Connection (pink)
Compressor Connection (pink)
TEMPERATURE CONTROL ADJUSTMENT FOR
HIGH ALTITUDE ONLY!
INSTALLATION / OPERATION INSTRUCTIONS