Spec Series Manual
9
STR•STA
•STG
LAE Control Sequence of Operation 
1. Cabinet is plugged in.   
  a. Display will illuminate.
  b. Interior lights will illuminate on Glass Door models only. (If lights do not come on please see   
  instructions on following pages(s).) Solid Door cabinet lights are controlled by door switch.
2.  After the LAE control preprogrammed time delay of 3 minutes (freezers only), the compressor and evaporator 
fan(s) will start if the control is calling for cooling.
      a. Control may be already preprogrammed from the factory so at the start of every compressor cycle or 
  during a defrost cycle, the condenser fan(s) will reverse for 30 seconds to blow dirt off the condensing 
 coil.
3.  The LAE control will cycle the compressor but may also cycle evaporator fan(s) on and off together 
determined by the Set-Point and Differential temperatures. (If the Set-Point needs to be changed due to 
conditions please see instructions on the following pages(s).)
a. The Set-Point is the preprogrammed temperature which shuts off the compressor.
b. The Differential is the preprogrammed temperature that is added to the Set-Point temperature that will 
start the compressor.
Example:  If the Set-Point is -9°F/-23°C and the Differential is 10°F/5°C
  (Set-Point) -9°F + 10 (Differential) = 1°F
 Or
  (Set-Point) -23°C + 5 (Differential) = -18°C
  The compressor and evaporator fan(s) will cycle off -9°F/-23°C 
  and back on at 1°F/-18°C
4.  The LAE control may be preprogrammed to initiate defrost by interval or at specifi c times of day. (If additional 
Defrost Intervals / Cycles are needed or a manual defrost is required due to conditions please see instructions 
on next page(s).)
  a.  At this time the “dEF” will appear on the display and compressor will turn off until a preprogrammed 
temperature or duration is reached. During this time for freezers only, evaporator fan(s) will also turn off 
and the coil heater and drain tube heaters will also be energized.
  b. After the preprogrammed temperature or duration for defrost has been reached there may be a short delay 
for both the compressor and evaporator fans to restart. At this time “dEF” may still appear on the display 
for a short time.
True Manufacturing recommends that only the Set-Point and/or 
Defrost Interval / Cycles may be adjusted due to certain conditions.
This sequence is NOT model specifi c.
Any questions please contact the Technical Service Department.
800-325-6152 • service@truemfg.com
STARTUP