Datasheet

MAX. No. of PSUs on 16A
CIRCUIT BREAKER
17 units (circuit breaker of type B) / 29 units (circuit breaker of type C) at 230VAC
SPECIFICATION
MODEL
TRU-12W
DC VOLTAGE RANGE
RATED CURRENT
RATED POWER
OUTPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
VOLTAGE RANGE
Note.4
FREQUENCY RANGE
EFFICIENCY
(Typ.)
AC CURRENT
INPUT
INRUSH CURRENT
(Typ.)
LEAKAGE CURRENT
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
OVER VOLTAGE
9~18V
700mA
12.6W
250mVp-p
±5.0%
±1.0%
±3.0%
500ms, 180ms / 230VAC
47 ~ 63Hz
79%
0.2A/230VAC
0.25mA / 240VAC
-30 ~ 70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +80 , 10 ~ 95% RH
±℃ 0.2%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltage. Please check the static characteristic for more details.
5. The power supply is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the
complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.
RIPPLE & NOISE
(max.)Note.2
VOLTAGE TOLERANCE
Note.3
ENVIRONMENT
SAFETY &
EMC
(Note 5)
PROTECTION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3.75KVAC
EMC IMMUNITY
Compliance to EN55015,EN61000-3-2 Class A,EN61000-3-3
Compliance to EN61547,EN61000-4-2,3,4,5,6,8,11; light industry level(surge 2KV), criteria A
EMC EMISSION
HOLD UP TIME
(Typ.)
20ms/230VAC at full load
20.7~ 24.3V
Protection type : Shut off o/p voltage, clamping by zener diode
77*40*29(L*W*H)
COLD START 70A(twidth=120 s measured at 50% Ipeak) at 230VACμ
ENEC EN61347-1, EN61347-2-13, EN62384 IP42 approved,
1145.7K hrs min. MIL-HDBK-217F (25 )
0.08Kg; 120pcs/11.8Kg/1.06CUFT
I/P-O/P:>100M Ohms / 500VDC / 25 / 70% RH
180 ~ 264VAC 254 ~ 370VDC
CURRENT ACCURACY
±8.0%
POWER FACTOR
(Typ.)
PF>0.5/230VAC at full load
12W Single Output Switching Power Supply