Cord Sets and Receptacles
Use only high quality, well-insulated, grounded extension
cords with the generator’s receptacles. Inspect extension
cords before each use.
Check the ratings of all extension cords before you use
them. Check the operator’s manuals of devices for the
manufacturer’s recommendations.
A double pole rocker switch main circuit breaker is provided
to protect the locking receptacle. If this circuit breaker is
tripped, all receptacles are disconnected.
120/240 Volt AC, 30 Amp, Locking Receptacle
Use a NEMA L14-30 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater). You can use the same 4-wire cord if you plan to run
a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single phase
loadsrequiringupto6,250wattsofpower(6.25kW)at
26.0 Amps for 240 Volts or two independent 120 Volt loads
at 26.0 Amps each. The outlet is protected by a two pole
rocker switch circuit breaker.
NOTICE
Receptacles may be marked with rating value
greater than generator output capacity.
• NEVERattempttopoweradevicerequiringmoreamperagethan
generator or receptacle can supply.
• DONOToverloadthegenerator.See Don’t Overload Generator.
120 Volt AC, 20 Amp, Duplex Receptacles
The generator has two 120 Volt, 20 Amp duplex receptacles.
Each receptacle is protected against overload by push-to-
reset circuit breakers.
Useeachreceptacletooperate120VoltAC,single-phase,
60Hzelectricalloadsrequiringupto2,400watts(2.4kW)at
20Ampsofcurrent.Usecordsetsthatareratedfor125Volt
ACloadsat20Amps(orgreater).Inspectcordsetsbefore
each use.
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
4-Wire Cord Set
WARNING Damaged or overloaded electrical cords
could overheat, arc, and burn resulting in death or
serious injury.
• ONLYusecordsratedforyourloads.
• Followallsafetiesonelectricalcords.
• Inspectcordsetsbeforeeachuse.