Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018)8
1 1 PageHeaderToc6 Installation
Installation in fire damper FK-EU
The RM-O-3-D duct smoke detector can be in-
stalled into the inspection access of FK-EU fire
dampers. For the exact position see the illustration
on the right.
If FK-EU is used as an air transfer damper accord-
ing to general building inspectorate licence
Z-6.50-2031:
Install the RM-O-3-D duct smoke detector in the
upper inspection access of the fire damper.
Proceed as follows:
1. ③
②
④
panel is used for centering).
2. Remove the inspection access panel by turning
and lifting it.
3. ①
⑤
adapter.
4. Connect the fire damper electrically to the duct
smoke detector, siehe „Elektrische Installation“
auf Seite 10.
Note:
Older FK-K90 and FK-EU fire dampers may have
an inspection access panel made of metal.
In this case you can remove the inspection access
panel and install the duct smoke detector with
washers and wing nuts in the fire damper (no
adapter required).
①
②
damper
③
Galvanised: A00000043410
Stainless steel: A00000043411
④
⑤
①
③
④
②
⑤
Installation in FK-EU
H 200 – 320 H 200 – 800
Installation location based on height
H