Tus neeg siv phau ntawv
Operating manual RM-O-3-D / Technical leaflet no. M375DD8 (05/2018) 7
4 Technical data
RM-O-3-D
EMC immunity to
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
Supply voltage
230 V AC + 10 / – 15%
50/60 Hz
or
24 V DC ± 6%
Power rating
3 VA
Micro fuse
T 100 L 250 V
Protection level
IP 42
Ambient temperature
0 °C … + 60 °C
Airflow velocity:
1 m/s ... 20 m/s
Acceptable humidity
condensation
Alarm threshold for
increased
contamination
> 70%
System monitoring
• > 90% contaminated
• No duct smoke
detector
• Data transmission to
duct smoke detector
has failed
Alarm relay contact
(release,
contamination)
250 V 2 A
Weight
0 . 7 kg
5 Transport, storage and
packaging
Delivery check
Check delivered items immediately after arrival for
transport damage and completeness. In case of
any damage or an incomplete shipment, contact
the shipping company and your supplier immedi-
ately.
A complete shipment includes:
• Duct smoke detector RM-O-3-D
• Operating and installation manual
Transport on site
If possible, take the product in its transport packag-
ing up to the installation location.
Storage
For temporary storage please note:
• Remove the plastic wrapping
• Protect the product from dust and contamination.
• Store the product in a dry place and away from
direct sunlight.
• Do not expose the product (not even with its
packaging) to the effects of weather.
• Do not store the product below -40 °C or above
50 °C.
Packaging
Properly dispose of packaging material.