Installation and operating manual Duct smoke detector RM-O-3-D to provide the control input signal for fire dampers and smoke protection dampers General building inspectorate licence Z-78.6-125 Operating manual RM-O-3-D / Technical leaflet no.
Contents 1 2 General information 3 Other applicable documentation __________ 3 Symbols used in this manual _____________ 3 Symbols used on the RM-O-3-D duct smoke detector _____________________________ 3 Safety and correct use 4 General information regarding safety _______ 4 Standards and guidelines________________ 4 Repair and replacement parts ____________ 4 Environmental protection ________________ 4 Correct use ___________________________ 4 Incorrect use __________________________ 4 Residual risks __
1 General information This operating manual describes the following variants of the duct smoke detector: • RM-O-3-D for 24 V DC supply • RM-O-3-D for 230 V AC supply To ensure correct functioning of the RM-O-3-D duct smoke detector it is essential to read the provided operating manual before starting any work, and to comply with it. This manual must be given to the system owner when handing over the system. The system owner must include the manual with the system documentation.
2 Safety and correct use General information regarding safety Correct use Only specialist personnel are allowed to perform the described work on the duct smoke detector. Only skilled qualified electricians are allowed to work on the electrical system.
3 Product description Functional description To prevent smoke from spreading in buildings, it is extremely important that it is detected at an early stage. The RM-O-3-D duct smoke detector is used to signal to and release fire dampers and smoke protection dampers. The duct smoke detector operates on the principle of light scattering and detects the smoke regardless of its temperature so that fire dampers can be closed before the release temperature is reached.
1 3 Produktbeschreibung 1 PageHeaderToc Operating status LEDs Operating status LED Red Yellow Alarm relay Signal relay 4 2 3 1 Damper blade position Green Ready Supply voltage OK No voltage 3 3 3 3 3 3 4 4 4 4 4 4 1 1 1 1 1 1 LED on LED off LED blinking 6 2 2 Supply voltage OK Electrical error No duct smoke detector – Alarm - immediate release – 2 Contamination 70% ....
4 Technical data RM-O-3-D 5 Transport, storage and packaging Delivery check EMC immunity to EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 Supply voltage 230 V AC + 10 / – 15% 50/60 Hz or 24 V DC ± 6% Check delivered items immediately after arrival for transport damage and completeness. In case of any damage or an incomplete shipment, contact the shipping company and your supplier immediately.
1 PageHeaderToc Installation The RM-O-3-D duct smoke detector can be installed into the inspection access of FK-EU fire dampers. For the exact position see the illustration on the right. If FK-EU is used as an air transfer damper according to general building inspectorate licence Z-6.50-2031: Install the RM-O-3-D duct smoke detector in the upper inspection access of the fire damper. Proceed as follows: 1. ③ ② ④ panel is used for centering). 2. Remove the inspection access panel by turning and lifting it.
2 6 Einbau 1 PageHeaderToc Installation into a duct or an extension piece Duct installation ① Proceed as follows to install the RM-O-3-D duct smoke detector: ② ③ Note The sensor head has to be permanently in the airflow as otherwise its function will be impaired. Consequently: • 1.5 × H minimum distance between duct smoke detector and any bend, control unit or other obstacle. • Place the duct smoke detector in the upper third of the duct (not near a corner). 1.
1 7 1 PageHeaderToc Electrical installation 230 V AC supply voltage Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. • Only skilled qualified electricians are allowed to work on the electrical system. • Switch off the power supply before working on any electrical equipment.
2 7 Elektrische 1 PageHeaderToc Installation 8 24 V DC supply voltage ① L1 L2 L1 N PE PE N L1 + 24 V DC – L4 – + 1 2 L3 3 4 1 2 – + ② ③ 5 – 250 V AC / DC N(–) ⑥ ④ – + S1 S2 S3 S4 S5 S6 ⑦ ⑤ ⑥ ⑦ A functional test should be carried out before commissioning, then every 12 months and after any modification, e.g. repair. Without smoke Press the test/reset push button on the duct smoke detector or in the engineering room (option).
9 10 Cleaning Maintenance Danger! Danger! Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. • Only skilled qualified electricians are allowed to work on the electrical system. • Switch off the power supply before working on any electrical equipment. Danger of electric shock! Do not touch any live components! Electrical equipment carries a dangerous electrical voltage. • Do not open the casing for cleaning.