MODEL RT2000 (X2) INSTALLATION GUIDE
POWER SUPPLY CORD -
SPECIFICATIONS
For European applications, the
power supply cord must conform to

1. Two-conductor with Physical
Earth (PE) ground.
2. IEC 320 molded connector on
one end and molded plug on
the other end.
3. Certified for country of
installation.
4. Rated minimum H05VV-F with
minimum 0.75 mm2 (except
where specific countries
require 1.0 mm2) conductors.
5. Maximum length: 3 meters.
Power Outlet Accessibility

outlet to supply power to the ATM, make sure the following requirements
are met:
1. The outlet is located near the equipment.
2. AC power for the terminal should come from a dedicated source with an
isolated ground. The ATM is designed to work on an IT (Isolated-Terra)
type power system having a phase-to-phase voltage not exceeding 240
volts.
3. The outlet is easily accessible and will not be blocked once the equipment
is installed.