User Manual

19
6.5 Bypass Range Setup
BYPASS RANGE: Sets the allowable voltage deviation (in percentage %) from nominal input voltage that is acceptable for
the unit to go to bypass in a fault condition. If the voltage goes outside the range, the unit will not go to bypass. If the unit
is already in bypass, it will turn the output off. The factory setting of 15% of 230V is compatible with the vast majority of
networking equipment.
Bypass Range Table
5% to 15% = -5%, +5% to -15%, +15%
HI 1 = -20% to +15%
HI 2 = -25% to +15%
HI 3 = (120V to 226V)
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second to
advance to the next
setup screen
Press the button
for 0.1 second to
advance to the next
setup screen
Press the button
for 0.1 second to
advance to the next
setup screen
Press the button
for 0.1 second to
advance to the next
setup screen
Set 5%
(-5% ~ +5%)
Set 6%
(-6% ~ +6%)
Set 7%
(-7% ~ +7%)
Set 8%
(-8% ~ +8%)
6. UPS Setup and Configuration
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second to
advance to the next
setup screen
Set 9%
(-9% ~ +9%)