6.4 Frequency Conversion Setup
During frequency converter mode, the bypass output is disabled and the inverter output frequency is fixed as the user’s
inverter frequency setting. The inverter output frequency will not synchronize with the input frequency, even if input frequency
is within +/-3 Hz of the inverter frequency setting. If there is an internal fault, the UPS will shut down directly without
transferring to Bypass Mode. While in frequency converter mode, the output load will be derated by 30%.
Note: Remove the load from the output before setting up frequency conversion. Do not attempt to change frequency with an attached load.
Frequency Conversion Setup for On-line Mode / Battery Mode
The frequency converter cannot be set under the on-line or battery modes. As a result, the LCD will display a warning message
when the user attempts to set this item.
Press the button
for 0.1 second
After 3 seconds
Press the button
for 0.1 second
Press the button
for 0.1 second
Press the button
for 0.1 second to
advance to the next
setup screen
Press the button
for 0.1 second to
advance to the next
setup screen
Set ON
Default
Setting
Frequency Conversion Setup for Standby Mode / Bypass Mode
6. UPS Setup and Configuration