User Manual
14
6.1 Setup Menu
Press the scrolling button for more than 3 seconds to enter the setup menu.
Note: Only qualified service personnel may perform setup actions. During setup, the following items can be adjusted:
1. Inverter voltage
2. Inverter frequency
3. Frequency converter
4. Bypass range
5. Economy mode
6. Alarm disable
7. Overload alarm
For setup procedures, refer to the following:
1. Press the scrolling button for more than 3 seconds to enter the setup menu.
2. Press the scrolling button for 0.1 second to change the parameter.
3. Press the confirmation button for 0.1 second to confirm your parameter.
4. You can skip to the next setup item by pressing the cancel button for 0.1 second.
5. In setup, press the scrolling button for more than 3 seconds. The LCD will go to the original display.
6. In setup, if no button is pressed for more than 2 minutes, the LCD will exit from the setup menu and return to the original
display.
This UPS supports a variety of advanced configuration options that can be accessed via the front panel LCD screen.
Configuration and information items include Inverter Voltage, Inverter Frequency, Frequency Conversion, Bypass Range,
Economy Mode, Alarm Setup and Overload Alarm Setup. Some settings cannot be changed in certain operation modes. Refer
to the table below for details:
Setup Item Standby Mode On-line Mode Bypass Mode Battery Mode
Inverter Voltage Yes No Yes No
Inverter Frequency Yes No Yes No
Frequency Converter Yes No Yes No
Bypass Range Yes Yes Yes Yes
Economy Mode Yes Yes Yes Yes
Alarm Disable Yes Yes Yes Yes
Overload Alarm Yes Yes Yes Yes
Note: Only qualified service personnel may perform setup actions.
6. UPS Setup and Configuration