Product Data Sheet / Brochure

Output Volt Amp Capacity (VA) 2000
Output kVA Capacity (kVA) 2
Output Watt Capacity (Watts) 1800
Output kW Capacity (kW) 1.8
Output Capacity Details OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 1 minute; 150%
load for 30 seconds; Loads greater than 150% trigger immediate switchover to BYPASS (when input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when input voltage and frequency are OUTSIDE bypass
limits)
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
220V; 230V; 240V
Nominal Voltage Details 230V default
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency when input is
40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE:
Output is regulated to +/-0.05Hz of selected nominal.
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Output Receptacles (7) C13
Included Output Power Cables Includes three C13 to C14 power cables
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery
Mode)
Pure Sine wave
INPUT
Rated input current (Maximum Load) 9.8A 220V; 9.3A 230V; 8.9A 240V
Nominal Input Voltage(s) Supported 220V AC; 230V AC; 240V AC
Nominal Input Voltage Description 230V factory default
UPS Input Connection Type C14 inlet
Input Circuit Breakers 20A
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3.0
Recommended Electrical Service 230V
Input Phase Single-Phase