Product Data Sheet / Brochure
Specifications
Included PDUMVROTATEBRKT allows mounting with rear-facing outlets
●
TAA-Compliant
Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases
●
OVERVIEW
UPC Code 037332205346
PDU Type Monitored
INPUT
PDU Input Voltage 208/230V
Recommended Electrical Service Single-phase 16/20A 230/208V service
Maximum Input Amps 16
Maximum Input Amps Details Agency derated to 16A continuous
Input Connection Type C20 inlet accepts included L6-20P input cable. Alternate C19 input cordsets supported.
PDU Plug Type NEMA L6-20P; IEC-320 C20
Input Phase Single-Phase
Input Cord Length (ft.) 10
Input Cord Length (m) 3.05
OUTPUT
Output Capacity Details 3.7kW (230V), 3.3kW (208V) / 16A total capacity; 16A max per C19 outlet; 12A (10A CE) max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (18) C13; (2) C19
Output Nominal Voltage 208/230V
Overload Protection n/a
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Digital meter reports PDU output current in amps, Scroll IP-address information; Display can be rotated 180 degrees
for installation with the input cable at the top
Front Panel LEDs n/a
Switches Press the SCROLL IP / ROTATE button and release after one second to display the configured IP address in 2 digit
intervals; Press and release after two seconds to rotate the display 180 degrees
PHYSICAL
3 / 4