User's Manual

Highly efficient operation in optional Economy Mode setting, saving BTU heat output and energy costs.
Innovative design makes unit adaptable to rackmount, tower, or stacking applications
Uses only 2 rack spaces (2U) in standard 19-inch rack
Optional 2-9USTAND kit enables upright tower placement
Optional 2POSTRMKITWM enables 2-post rackmount or wallmount installation
Supports simultaneous communications via built-in USB port, DB9 serial port and SNMPWEBCARD slot
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Slot for optional SNMP/web card (Part Number: SNMPWEBCARD)
PowerAlert unattended shutdown software and communications cabling included
Compatible with Tripp Lite's WatchDog software
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Built-in Emergency Power Off (EPO) interface with cable
Single-line tel/DSL or Ethernet network surge suppression
Integrated 2-bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each
bank has 3 outlets)
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
1500
Output kVA capacity
(kVA)
1.5
Output Watt Capacity
(watts)
1200
Output kW capacity 1.2
Output power factor 0.8
Crest Factor 3:1
Nominal Output
Voltage(s) Supported
200V; 220V; 230V; 240V
Nominal Voltage
details
230V default
Frequency
compatibility
50 / 60 Hz
Frequency
compatibility details
Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start
Output voltage
regulation (line mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
6 C13 outlet(s)
Included output
power cables
Includes 2 C13 to C14 output power cables
Built-in controllable
switched load banks
Two switchable three-outlet C13 load banks