Datasheet
Installation Form Factors Supported
with Optional Accessories
2 post rackmount (2POSTRMKITHD); Tower (2-9USTAND)
Optional Mounting Accessory Notes 2 sets of 2POSTRMKITHD required for 2 post rackmount installation of separate UPS and transformer components
Primary Form Factor Rackmount
UPS Power Module Dimensions
(hwd, in.)
6.85 x 17.5 x 20.7
UPS Power Module Dimensions
(hwd, cm)
17.4 x 44.5 x 52.6
Installed Whole System Maximum
Rack Depth (in.)
21.8
Installed Whole System Maximum
Rack Depth (cm)
55.4
Rack Height (U Spaces) 6
UPS Power Module Weight (lbs.) 116.2
UPS Power Module Weight (kg) 52.8
Stepdown Transformer Dimensions
(hwd / in.)
3.5 x 17.5 x 21.8
Stepdown Transformer Dimensions
(hwd / cm)
8.8 x 44.5 x 55.4
Stepdown Transformer Weight (lbs.) 72.6
Stepdown Transformer Weight (kg) 33
UPS Shipping Dimensions (hwd / in.) 22.2 x 23.6 x 29.1
UPS Shipping Dimensions (hwd /
cm)
56.4 x 59.9 x 73.9
Shipping Weight (lbs.) 232.1
Shipping Weight (kg) 105.4
Cooling Method Fans
UPS Housing Material Steel
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 1767
AC Economy Mode BTU / Hr. (Full
Load)
765
AC Mode Efficiency Rating (100%
Load)
90%
AC Economy Mode Efficiency Rating
(100% Load)
96%
5 / 6