Datasheet
BATTERY
Full Load Runtime (min.) 2 minutes (5400 watts)
Half Load Runtime (min.) 8.5 minutes (2700 watts)
Expandable Battery Runtime Runtime is expandable with external battery packs
External Battery Pack Compatibility
BP192V1037C-1PH; BP192V12-3U; BP192V1407C-1PH; BP192V557C-1PH; BP192V787C-1PH; BP192V5RT2U
(limit 1)
DC System Voltage (VDC) 192
Battery Recharge Rate (Included
Batteries)
6 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
RBC5-192
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable internal batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction Corrects overvoltages as high as 300V (<90% load) and 280V (full load)
Undervoltage Correction Corrects undervoltages as low as 100 (<50% load) and 155V (full load); derates linearly
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Switches
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass
switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without
disrupting power to connected loads
Alarm Cancel Operation Alarm cancel switch
Audible Alarm Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Front Panel LCD No
LED Indicators
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
SURGE / NOISE SUPPRESSION
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description
4 post rackmount installation accessories included (2 sets)
4 / 6