Datasheet
OUTPUT
Output Capacity Details
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as the overload is cleared
Output Volt Amp Capacity (VA) 6000
Output kVA Capacity (kVA) 6.0
Output Watt Capacity (Watts) 5400
Output kW Capacity (kW) 5.4
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
120V; 208V; 240V
Nominal Voltage Details
This configuration requires the Power Module be set to 208 or 240V output voltage; included step-down transformer
supports 120V output (when the voltage-selection switch on the transformer module is set to match the 208 or 240V
power module setting)
Frequency Compatibility 60 Hz
Frequency Compatibility Details Output frequency regulation +/- 0.05Hz (free running)
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles (4) 5-15R; (8) 5-15/20R; (1) L6-30R; Hardwire
Output Receptacle Details
Hardwire input and output connections are mounted on a detachable PDU backplate with bypass switch to enable
hot-swappable power module replacement
Output Circuit Breakers
Low voltage 20A breakers on the transformer module protect 4 5-15/20R outlets each; Low voltage 15A breakers
protect 2 5-15/20R outlets each
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)
Nominal Input Voltage(s) Supported 208V AC; 240V AC
Nominal Input Voltage Description Factory configured to 208V
UPS Input Connection Type Hardwire
UPS Input Connection Description 3 wire single phase input (L1, L2, G)
Recommended Electrical Service 40A (200/208v); 30A (220/230/240v)
Input Phase Single-Phase
3 / 6