Output Capacity Details
6,000VA / 4200W (240V) / 5400VA / 4200W (208V); Supports up to 105% load continuously in double conversion
mode, 106 to 125% for 3 minutes, 126 to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode
operation to support equipment directly from mains power; Double conversion mode is automatically restored as
the overload is cleared
Output Volt Amp Capacity (VA) 6000
Output kVA Capacity (kVA) 6
Output Watt Capacity (Watts) 4200
Output kW Capacity (kW) 4.2
Power Factor 0.7
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
120V; 208V; 240V
Nominal Voltage Details 240/120 or 208/120 split phase output
Frequency Compatibility 60 Hz
Output Voltage Regulation (Line
Mode)
+/- 3%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Output Receptacles (8) 5-15/20R; (2) L6-20R; (2) L6-30R
Output Circuit Breakers
20A branch rated breakers (x4) protect 2 5-15/20R outlets each, 20A double pole breakers (x2) protect one L6-20R
each, L6-30R outlets are unbreakered
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 24A
Nominal Input Voltage(s) Supported 208V AC / 120V AC (4 wire split single phase); 240V AC /120V AC (4 wire split single phase)
UPS Input Connection Type L14-30P
UPS Input Connection Description 4 wire split-phase input (L1, L2, N, G)
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3
Recommended Electrical Service 30A 208/120V Split Phase
Input Cord Length (m) 3
Input Phase Single-Phase