Datasheet

ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 1412.3
AC Economy Mode BTU / Hr. (Full
Load)
911.5
AC Mode Efficiency Rating (100%
Load)
91%
AC Economy Mode Efficiency Rating
(100% Load)
94%
Operating Elevation (ft.) 0-3000m (0 to 10,000 ft.)
Audible Noise 60 dBA at front side 1 meter
COMMUNICATIONS
Communications Interface DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description RS232 and contact closure communications are located on two separate DB9 ports
PowerAlert Software Included
Communications Cable DB9 cable included
LINE / BATTERY TRANSFER
Transfer Time No transfer time (0 ms.) in online, double-conversion mode
Transfer Time (Economy Mode) Less than 1ms typical power failure response in optional economy mode
Low Voltage Transfer to Battery
Power (Setpoint)
156
High Voltage Transfer to Battery
Power (Setpoint)
276
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features Automatic inverter bypass; Hot swappable batteries
Green Energy-Saving Features High efficiency economy mode operation; Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); CE; Tested to GOST (Russia);
Tested to SASO (Saudi Arabia); Tested to IRAM (Argentina); Meets FCC Part 15 Category A (EMI); ROHS
(Restriction of Hazardous Substances)
WARRANTY
5 / 6