Datasheet

Output Circuit Breakers 40A double-pole
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 30A
Nominal Input Voltage(s) Supported 200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection Type Hardwire
UPS Input Connection Description
Supports North American 208/240V input (L1,L2,G) and International 230/220/240V (L,N,PE) input wiring; Optional
SUPDM11 backplate adds 2 L6-30R outlets and L6-30P input cord
Input Circuit Breakers 40A double-pole
Recommended Electrical Service 30A 208/220/230/240V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 8 min. (4200w)
Half Load Runtime (min.) 20 min. (2100w)
Expandable Battery Runtime
Includes one non-expandable BP240V7RT3U (limit 1) external battery pack. No additional BP240V7RT3U external
battery packs can be connected to the host UPS, beyond the one included with the
SU6000RT3UHV
UPS bundle.
All additional battery packs connected beyond the included BP240V7RT3U, must be
BP240V10RT3U
,
BP240V557C-1PH
,
BP240V787C-1PH
,
BP240V1037C-1PH
or
BP240V1407C-1PH
External Battery Pack Compatibility
BP240V10RT3U
;
BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH
;
BP240V1407C-1PH
DC System Voltage (VDC) 240
Battery Recharge Rate (Included
Batteries)
Less than 6 hours from 10% to 80% (typical, full load discharge)
Battery Replacement Description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction 2% output voltage regulation during overvoltages to 276
Undervoltage Correction 2% output voltage regulation during undervoltages to 156
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions
Alarm Cancel Operation Alarm cancel switch
Audible Alarm Unique audible alarms for all major UPS, environmental and power conditions (see manual)