Datasheet

Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Output frequency matches input nominal on startup
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles Hardwire
Output Receptacle Backplate
Options
Optional backplates SUPDM12 (for 208v nominal), SUPDM14 (for 240v nominal), SUPDM16 (for 208v nominal) add
low and high voltage outlets, plus L6-30P input cord
Output Circuit Breakers 40A double-pole
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 30A
Nominal Input Voltage(s) Supported 208V AC; 240V AC
UPS Input Connection Type Hardwire
UPS Input Connection Description
3 wire single phase input (L1, L2, G); optional, country-specific backplates SUPDM12 (for 208v nominal), SUPDM14
(for 240v nominal), SUPDM16 (for 208v nominal) add low and high voltage outlets, plus L6-30P input cord
Input Circuit Breakers 40A double-pole
Recommended Electrical Service 30A 208V or 240V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 8 min. (4200w)
Half Load Runtime (min.) 20 min. (2100w)
Expandable Battery Runtime Supports extended runtime with optional external battery packs
External Battery Pack Compatibility
BP240V10RT3U
;
BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH
;
BP240V1407C-1PH
DC System Voltage (VDC) 240
Battery Recharge Rate (Included
Batteries)
Less than 6 hours from 10% to 80% (typical, full load discharge)
Battery Replacement Description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction 2% output voltage regulation during overvoltages to 276
Undervoltage Correction 2% output voltage regulation during undervoltages to 156
3 / 6