Datasheet
UPS Power Module Dimensions
(hwd, cm)
17.4 x 44.5 x 52.6
Installed Whole System Maximum
Rack Depth (in.)
20.75
Installed Whole System Maximum
Rack Depth (cm)
52.7
Rack Height (U Spaces) 6
UPS Power Module Weight (lbs.) 113.6
UPS Power Module Weight (kg) 51.6
Stepdown Transformer Dimensions
(hwd / in.)
3.5 x 17.5 x 20.75
Stepdown Transformer Dimensions
(hwd / cm)
8.8 x 44.4 x 52.7
Stepdown Transformer Weight (lbs.) 76
Stepdown Transformer Weight (kg) 34.5
UPS Shipping Dimensions (hwd / in.) 22 x 25 x 30
UPS Shipping Dimensions (hwd /
cm)
55.9 x 63.5 x 76.2
Shipping Weight (lbs.) 278
Shipping Weight (kg) 126.2
Cooling Method Fan
UPS Housing Material Sheet metal
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range 5 to 122 F / -15 to 50 C
Relative Humidity 5% to 90% (non-condensing)
AC Mode BTU / Hr. (Full Load) 1767
AC Economy Mode BTU / Hr. (Full
Load)
638
AC Mode Efficiency Rating (100%
Load)
90%
AC Economy Mode Efficiency Rating
(100% Load)
96%
Operating Elevation (ft.) 0 to 6560 ft. / 0 to 2000 m
Audible Noise 65 dB at 1m front side
Operating Elevation (m) 0-2000 m
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
5 / 6