Datasheet
Output Capacity Details
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as the overload is cleared
Output Volt Amp Capacity (VA) 5000
Output kVA Capacity (kVA) 5.0
Output Watt Capacity (Watts) 4500
Output kW Capacity (kW) 4.5
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
120V; 208V
Nominal Voltage Details
This configuration requires the Power Module be set to 208V output voltage; Included step-down transformer
supports 120V output
Frequency Compatibility 60 Hz
Frequency Compatibility Details Output frequency regulation +/- 0.05Hz (free running)
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles (12) 5-15/20R; (2) L6-20R; (2) L6-30R
Output Circuit Breakers
High voltage 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered; Low voltage 20A breakers
protect 3 5-15/20R outlets each
Output AC Waveform (AC Mode) Pure sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 24A (208V)
Nominal Input Voltage(s) Supported 208V AC
UPS Input Connection Type L6-30P
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3
Recommended Electrical Service 30A
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 3.5 minutes (4500w)
Half Load Runtime (min.) 11 minutes (2250w)
3 / 6