Datasheet

UPS Shipping Dimensions (hwd / in.) 12.7 x 23.6 x 29.1
UPS Shipping Dimensions (hwd /
cm)
32.3 x 60 x 73.9
Shipping Weight (lbs.) 151.8
Shipping Weight (kg) 68.9
Cooling Method Fan
UPS Housing Material Steel
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 5% to 90% (non-condensing)
AC Mode BTU / Hr. (Full Load) 1767
AC Economy Mode BTU / Hr. (Full
Load)
638
AC Mode Efficiency Rating (100%
Load)
90%
AC Economy Mode Efficiency Rating
(100% Load)
96%
Operating Elevation (ft.) 0 to 6560 ft. / 0 to 2000 m
Audible Noise 65 dB at 1m front side
Operating Elevation (m) 0-2000 m
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description
Two contact closure monitoring options available - RELAYIOCARD with six configurable contact closure outputs
(uses UPS card slot) and RELAYIOMINI with 3 configurable contact closure outputs (requires removal of USB port
module)
PowerAlert Software Included
Communications Cable USB, DB9 serial and EPO cables included
WatchDog Compatibility Yes
LINE / BATTERY TRANSFER
Transfer Time No transfer time (0 ms.) in online, double-conversion mode
Transfer Time (Economy Mode) 8 ms. typical power failure response in optional economy mode
Low Voltage Transfer to Battery
Power (Setpoint)
156V (full load) / 100V (50% load or less, derates linearly)
High Voltage Transfer to Battery
Power (Setpoint)
280V (full load) / 300V (90% load or less)
5 / 6