Datasheet

UPS Shipping Dimensions (hwd /
cm)
76.2 x 63.5 x 83.8
Shipping Weight (lbs.) 288
Shipping Weight (kg) 130.8
Cooling Method Fan
UPS Housing Material Steel
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 1322.2
AC Economy Mode BTU / Hr. (Full
Load)
759.6
AC Mode Efficiency Rating (100%
Load)
90%
AC Economy Mode Efficiency Rating
(100% Load)
94%
COMMUNICATIONS
Communications Interface DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description RS232 and contact closure communications are located on two separate DB9 ports
PowerAlert Software Included
Communications Cable DB9 cable included
LINE / BATTERY TRANSFER
Transfer Time No transfer time (0 ms.) in online, double-conversion mode
Low Voltage Transfer to Battery
Power (Setpoint)
156
High Voltage Transfer to Battery
Power (Setpoint)
276
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features Automatic inverter bypass; Hot swappable batteries
Green Energy-Saving Features High efficiency economy mode operation; Schedulable daily hours of economy mode operation
CERTIFICATIONS