Datasheet
Output Receptacles (12) 5-15/20R; (2) L6-20R; (2) L6-30R
Output Circuit Breakers
20A breakers (x4) on transformer module protect 3 5-15/20R outlets each, 20A breaker on power module protects
L6-20R outlets, L6-30R outlets are unbreakered
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 24A (208V)
Nominal Input Voltage(s) Supported 208V AC
UPS Input Connection Type L6-30P
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3
Recommended Electrical Service 30A 208V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 8 min. (3500w)
Half Load Runtime (min.) 20 min. (1750w)
Expandable Battery Runtime Supports extended runtime with optional external battery packs
External Battery Pack Compatibility
BP240V10RT3U
;
BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH
;
BP240V1407C-1PH
DC System Voltage (VDC) 240
Battery Recharge Rate (Included
Batteries)
Less than 6 hours from 10% to 80% (typical, full load discharge)
Battery Replacement Description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction 2% output voltage regulation during overvoltages to 276
Undervoltage Correction 2% output voltage regulation during undervoltages to 130
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions
Alarm Cancel Operation Alarm cancel switch
Audible Alarm Unique audible alarms for all major UPS, environmental and power conditions (see manual)
LED Indicators
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
3 / 6