Datasheet

Accepts input voltages between 156 and 276, regulating output within 2% of 208 - plus 120V nominal voltage
Supports connected equipment during blackouts for 20/8 minutes at half/full load levels, runtime is further expandable with optional external battery packs
Network interfaces support simultaneous communications via 2 DB9 ports and SNMPWEBCARD slot
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number
of additional servers over IP
Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery
capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control
Built-in Emergency Power Off (EPO) interface with cable
Includes 17 built-in output receptacles (3 L6-30R w/one L6-30R used for transformer connection, 2 L6-20R, 12 NEMA 5-15/20R)
L6-30P input plug-in connection
Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical conditions
Front panel switches enable power on/off control, self-test and alarm cancel functions
Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures, optional 2POSTRMKITHD supports 2 post rackmount installation
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Specifications
General Info
RoHS Y
OUTPUT
Output Capacity Details
Supports up to 102% load continuously in double conversion mode, 102 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as the overload is cleared
Output Volt Amp Capacity (VA) 5000
Output kVA Capacity (kVA) 5
Output Watt Capacity (Watts) 3500
Output kW Capacity (kW) 3.5
Power Factor 0.7
Crest Factor 3:1
Nominal Output Voltage(s)
Supported
120V; 208V
Nominal Voltage Details
This configuration requires the Power Module be set to 208V output voltage; Included step-down transformer
supports 120V output
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Output frequency matches input nominal on startup
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
2 / 6