Datasheet
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
Hardwire
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
97A (per phase, on-line)
Nominal Input
Voltage(s) Supported
120V / 208V 3 phase wye
UPS input
connection type
Hardwire
UPS input
connection
description
120/208V (3-Phase, 4 Wire, wye)
BATTERY
Full load runtime
(minutes)
5.5 min. (32kw)
Half load runtime
(minutes)
13 min. (16kw)
Expandable battery
runtime
Supports extended runtime with optional external battery packs
External battery
pack compatibility
BP480V26B; BP480V40C; BP480V55; BP480V78; BP480V103; BP480V140
Expandable runtime
description
External battery pack wiring is contractor supplied
DC system voltage
(VDC)
240
Battery recharge
rate (included
batteries)
Less than 4 hours from 10% to 90%
Battery replacement
description
Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Online, double-conversion power conditioning
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 150/260 (3-Phase, 4-Wire, wye),
reducing output within 1% of nominal
Undervoltage
correction
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 94/163
(3-Phase, 4-Wire, wye)
LEDS ALARMS & SWITCHES
LED Indicators 4-LED Display: Displays normal AC input, on battery power, bypass input and fault conditions
Alarms Alarms signal a variety of operational conditions: low-battery, overload, shutdown, bypass and more