Datasheet

Frequency
compatibility details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
Output voltage
regulation (line
mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
2 L6-30R outlet(s); 8 C19 outlet(s)
Output circuit
breaker
Two built-in 30A breakers protect one L6-30R outlet each; Eight built-in 20A breakers protect one C19 outlet each
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
112.2A (200V), 108A (208V), 102A (220V), 97.6A (230V), 93.6A (240V)
Nominal Input
Voltage(s) Supported
200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS input
connection type
Hardwire
UPS input
connection
description
3 wire single phase input (L1, L2, G)
Recommended
Electrical Service
120A
BATTERY
Full load runtime
(minutes)
4.3 minutes (18,000 watts)
Half load runtime
(minutes)
12.5 minutes (9000 watts)
Expandable battery
runtime
Runtime is expandable with external battery packs
External battery
pack compatibility
BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH
Expandable runtime
description
For best results, add external batteries in multiples of two so that both included 10kVA power modules have an equal
number and type of connected battery packs
DC system voltage
(VDC)
240
Battery recharge
rate (included
batteries)
Less than 8 hours from 10% to 90%
Battery replacement
description
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION