Datasheet

Nominal Input
Voltage(s) Supported
120V AC
UPS input connection
type
5-15P
Input circuit breaker 15A
UPS Input cord length
(ft.)
6
UPS Input cord length
(m)
1.8
Recommended
Electrical Service
15A 120V
BATTERY
Full load runtime
(minutes)
7 min. (980w)
Half load runtime
(minutes)
20 min. (490w)
Expandable battery
runtime
Extended runtime supported via optional external battery packs
External battery pack
compatibility
BP36V15-2U (limit 1); BP36V42-3U (multi-pack compatible)
DC system voltage
(VDC)
36
Battery recharge rate
(included batteries)
Less than 4 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC53
Battery Access Battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147
Overvoltage correction Input voltages between 128 and 147 are reduced by 12%
Undervoltage correction Input voltages between 93 and 107 are boosted by 14%
Severe undervoltage
correction
Input voltages between 75 and 92 are boosted by 30%
LEDS ALARMS & SWITCHES
LED Indicators 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION