Datasheet

Rated input current (at
maximum load)
6.1A (120V), 6.6A (110V), 7.2A (100V)
Nominal Input Voltage(s)
Supported
100V AC; 110V AC; 120V AC
UPS input connection
type
5-15P
UPS Input cord length (ft.) 6
UPS Input cord length (m) 1.8
Recommended Electrical
Service
15A 120V
BATTERY
Full load runtime
(minutes)
7 min. (650w)
Half load runtime
(minutes)
19 min. (325w)
DC system voltage (VDC) 24
Battery recharge rate
(included batteries)
Less than 6 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC24-SLT
Battery Access Battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 95 to 145
(120v), 87 to 133 (110v), 83 to 121 (100v)
Overvoltage correction Voltage reduction of 12% applies when input is 127 to 145 (120v), 116 to 133 (110v), 111 to 121 (100v)
Undervoltage correction Voltage boost of 14% applies when input is 95 to 108 (120v), 87 to 99 (110v), 83 to 90 (100v)
LEDS ALARMS & SWITCHES
LED Indicators 9 LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter
for load and battery charge level
Site wiring fault indication Rear panel site wiring fault LED
Alarms Audible alarm indicates power failure and overload conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel switch
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches
support nominal voltage selection
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
690
UPS AC suppression
response time
Instantaneous
UPS Dataline suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet