Datasheet
External PDU
redundancy options
*Auto Transfer Switch features utilizing the secondary PDU input cord are compatible with Smart Online UPS
models only
Output AC waveform
(AC mode)
Sine wave
INPUT
Nominal Input
Voltage(s) Supported
208V AC
UPS input connection
type
L6-30P
Input circuit breaker 30A double-pole
UPS Input cord length
(ft.)
10
UPS Input cord length
(m)
3
Recommended
Electrical Service
30A 208V
Input cord length (ft.) 10
Input cord length (m) 3
BATTERY
Full load runtime
(minutes)
16 min. (4000w)
Half load runtime
(minutes)
38 min. (2000w)
Expandable battery
runtime
Extended runtime supported via optional external battery packs
External battery pack
compatibility
BP48V60RT-3U (multi-pack compatible)
DC system voltage
(VDC)
48
Battery recharge rate
(included batteries)
Less than 4 hours from 10% to 90%
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 151 to 282
Overvoltage correction Input voltages between 240V and 282 are reduced by 12%
Undervoltage
correction
Input voltages between 180V and 199 are boosted by 12%
Severe undervoltage
correction
Input voltages between 151V and 179 are boosted by 24%
LEDS ALARMS & SWITCHES
LED Indicators 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms Audible alarm indicates power-failure, overload and low-battery conditions