Digital Load Meter
1
   Select Bank Button:Thisbutton
A
canbepressedtoshowtotalcurrentfor
eachbank.Pressingthisbuttononce
will display the total current for all of the 
Bank1outlets,locatednearesttothe
inputcord.TheLEDforBank1
D
 will 
illuminateandthetotalcurrentforBank
1outletswilldisplayinampsintheLED
Amps display 
C
.Pressingthisbutton
A
 a second time will produce the same 
resultsforBank2.Pressingthebuttona
thirdtimewilldisplaytotalPDUcurrent
andbothBank1andBank2LEDswill
light.Pressingthebuttonadditional
times will repeat the cycle.
 Ifyoupressandholdthisbuttonfor
4seconds,thenumbersintheLED
Amps display 
C
 will flip for mounting 
versatility.Theunitcanbemountedwith
thepowercordfacingthetoporbottom
whilestillbeingabletoreadthedisplay.
2
  Select Outlet Button: Thisbutton
B
canbepressedtoshowthecurrentforeach
individualoutlet.TheLEDlocatednexttotheselectedoutletandtheLEDfortheBank
towhichtheoutletbelongs(
D
 or 
E
)willashwhenthetotalcurrentforthatoutletis
displayed(inamps)ontheLoadMeterDisplay
C
. 
Pressingthisbuttonasecondtimewillproducethesameresultsforoutlet2,pressinga
third time for outlet 3 and so on through all the outlets.
 Ifyoupressandholdthisbutton
B
for4secondsyoucandisplaytheIPAddressassigned
totheunitintheLEDAmpsdisplay
C
. The default is no address assigned. If this is the 
case,“no address”willdisplay,oneletteratatime.IfthereisanIPAddressprogrammed,
theaddresswilldisplay1digitatatimewithdashes(-)representingdotsorperiods(.).