Owner`s manual
Thermal 2-Pole Breaker 
(PDUMNH32HV)
A B
4
2. Features
(PDUMNH30HV & PDUMNH32HV): The Digital Load 
Meter may be set using the Meter Select switch to display 
the PDU’s total connected load (all 16 outlets-both LEDs 
illuminated), or the load carried by either the upper bank 
(Bank 1 LED illuminated) or lower bank (Bank 2 LED 
illuminated) of 8 outlet receptacles. If you press and hold 
the mode selection switch A for 4 seconds, the unit’s IP 
address will display on the meter B. Note: If no IP address is 
assigned (default), “no address” will display, one letter at a 
time. If an IP address is assigned, it will display one digit at a 
time, with dashes (-) representing the dots (.) in the address.
Output Circuit Breakers: Two circuit breakers (one 
per outlet bank) protect connected equipment against 
dangerous system overloads. If the total load on either of the 
PDU’s outlet banks exceeds 20 amps, the associated circuit 
breaker will trip, cutting power to the entire outlet bank. 
Reduce the load on the outlet bank by unplugging some 
equipment; then switch the circuit breaker ON to restore 
power.
Longer 1U Mounting Brackets: Use these brackets to 
mount the 1U PDU horizontally in a standard rack or rack 
enclosure. The mounting depth can be adjusted by attaching 
the brackets to different positions on the PDU.
Shorter 0U Mounting Brackets: Use these brackets 
to mount the PDU in a 0U rack, wall or under-counter 
conguration for 1U PDU models.
2U Mounting Brackets: Use these brackets to mount the 
2U PDU horizontally in a standard rack or rack enclosure, or 
in an under-counter conguration.
Cord Retention Shelves (Optional): When installed on the 
PDU, these shelves provide secure attachment points for 
connected equipment power cords. Use the included cable 
ties to secure cords to the shelf.
Magnetic, 2-Pole Branch-Rated 
Breaker (PDUMNH30HV)
201110150-93-3050.indb 4 11/9/2011 11:13:07 AM