Owner`s manual

8
Features
Digital Load Meter (Ammeter): The digital load meter
displaystheloadinamps.ItmaybesetusingtheMeter
SelectswitchtodisplaythePDU'stotalconnectedload
(all16outlets-bothLEDsilluminated),ortheloadcarried
byeithertheupperbank(Bank1LEDilluminated)or
lowerbank(Bank2LEDilluminated)of8outlet
receptacles.FormodelswithSNMPNetworkCard
installed,pressandholdtheswitchtodisplaytheIP
addressoftheSNMPcardinthePDU.
Output Circuit Breakers: Twocircuitbreakers(oneper
outletbank)protectconnectedequipmentagainst
dangeroussystemoverloads.Ifthetotalloadoneitherof
thePDU'soutletbanksexceeds20amps(PDUMH30NET
&PDUMH32HVNET)or15amps(PDUMH30HVNET),the
associatedcircuitbreakerwilltrip,cuttingpowertothe
entireoutletbank.Reducetheloadontheoutletbankby
unpluggingsomeequipment,thenpressthecircuit
breakerin/settotheONpositiontorestorepower.
Cord Retention Shelves (Optional): Wheninstalledon
thePDU,theseshelvesprovidesecureattachmentpoints
forconnectedequipmentpowercords.Usetheincluded
cabletiestosecurecordstotheshelf.
Mounting Brackets: Thesedetachablebracketsenable
thePDUtobeinstalledina2Urackmountconfiguration
oranunder-counterconfiguration.
Factory Port: Theportisreservedforconfigurationby
factoryauthorizedpersonnelonly.Donotconnect
anything to the port.
Ground Connection: Usethistoconnectanyequipment
that requires a chassis ground.
PS/2 Port: UsethisporttoconnectaTrippLite
ENVIROSENSEenvironmentalsensortoprovideremote
temperature/humidity monitoring and a dry contact
interfacetocontrolandmonitoralarm,securityand
telecomdevices.ContactTrippLiteCustomerSupportat
773.869.1234fororderinginformation.Note: Do not
connect a keyboard or mouse to this port.
Meter Select
Bank 2
Bank 1
LOAD (AMPS)