Features continued
5
  Digital LED Display and  
Load Meter (Ammeter)
A
  3-Digit Display: Shows 
measured or calculated 
amperage,kilowattorvoltage
values.
B
  Enter Button: Scroll through 
DISPLAYandCONFIGURATION
optionsusingthisbutton.While
inDISPLAYmode,ashortpress
switches the display between 
AMPS,KWandVOLTS.Whilein
CONFIGURATIONmode,along
press changes configuration 
items(TEMPERATURE,AUTO
SCROLL,LEDBRIGHTNESS).
PressingtheEnter button and 
Mode button simultaneously 
displaystheunit’sIPaddress
(selectmodels).
C
  Mode Button: A short press of this button cycles through each of the modes 
(PRIMARY,SECONDARY,BANK,TEMP*,HUMIDITY*)ofthepresentcategory
(DISPLAYorCONFIGURATION)forbothprimaryandsecondaryinputs.Along
pressswitchesbetweenDISPLAYandCONFIGURATION.PressingtheMode 
button and Enterbuttonsimultaneouslydisplaystheunit’sIPaddress(select
models).
    *TEMP/HUMIDITY only available if optional ENVIROSENSE module is attached.
D
  Active Input LEDs: Indicate whether the primary or secondary active input is 
powering the output.
E
  2-Digit Display: Indicates whether the value shown on the 3-digit display 
representsprimary,secondary,bank,temperatureorhumidity.
 Display Modes:
    P: The 3-digit display is showing information related to the primary AC input. 
(UnitLEDsdictatewhatdataisshown.)
    S: The 3-digit display is showing information related to the secondary AC input. 
(UnitLEDsdictatewhatdataisshown.)
    b ‘n’:The3-digitdisplayisshowinginformationrelatedtotheoutputbank
number(‘n’).
    t ‘n’:The3-digitdisplayisshowingtemperatureforsensor(‘n’).(UnitsforForC
areconfiguredinCONFIGURATIONmode.)
    h ‘n’:The3-digitdisplayisshowinghumidityforsensor(‘n’).
ACTIVE INPUT
PRIMARY SECONDARY
AMP
b = BANK
t = TEMP
h = HUMIDITY
P = PRIMARY
S = SECONDARY
VOLT
KW
B
D
E
C
F
A