Remote Monitoring and Control
ModelsPDUMH30ATNETandPDUMH30HVATNETprovideremotemonitoring,outlet
controlandmoreviaWebbrowser,telnetandSNMP-basedNetworkManagement
Systems.FormoreinformationaboutconfigurationandoperationofthePDUviathe
PowerAlertWebbrowserinterface,refertotheSNMPWEBCARDUser'sGuide,
includedontheCD-ROMbundledwiththePDU.
Load "Ramping" on Startup: All models arrive from the factory programmed so
that,whenfirstpoweredup,theiroutletsturnoninsequentialorderatintervalsof
approximately250ms.Thispreventscircuitoverloadsbystaggeringthestartupof
multipledevices.ModelsPDUMH30HVATNETandPDUMH30ATNETsupportuser-
programmablestartupofoutlets,inanyorderortimeinterval.Thisensuresthat
networkitemsareturnedoninthepropersequence,withtheappropriatedelay,so
thatnetworkitemsarereliablydiscoveredonstartup.
Programmable Load "Shedding" During a Power Failure: In the event that the
primarypowersourcefailsandthePDUisrelyingonthesecondarypowersource,
load shedding allows you to program the shutoff of specific outlets at timed intervals.
Thisenablesyoutoturnofflesscriticalloads(monitors,forexample)tomaximizethe
UPSruntimeforthemostcriticalitems.