Owner`s manual
1-5
2-1
2-3
2-3
2-2
A
B
A
PDUMH20NET2
PDUMH15NET2
PDUMH20NET2
A
A
B
B
C
C
4
Installation continued
1-5
Cord Retention Shelf
Attachment (Optional): Use2
screws
A
to attach the cord
retention shelf
B
to the front
panelofthePDU.
Connecting the PDU
2-1
Connect Input Plug Adapters
(Optional – PDUMH20NET2
Only): ThePDUincludesan
adapterthatconvertsitsL5-20P
lockinginputplugtoastandard
5-20Pinputplug.Connectingthis
adapterisoptional.ThePDUwill
function normally without
connecting this adapter.
Note: The AC power source should not share a
circuit with a heavy electrical load (such as an air
conditioner or refrigerator).
2-2
Connect Input Power Cord
(PDUMH15NET2 and
PDUMH20NET2): Connect the
input plug
A
toacompatible
sourceofACpower,suchasa
UPSsystem,PDUorutilityoutlet.
ThePDUshouldbeprovidedwith
over-currentprotection:
PDUMH15NET2withamaximum
15Abranch-ratedprotection
device;PDUMH20NET2witha
maximum20Abranch-rated
protection device.
2-3
Equipment Power Cord
Connection: Insert power cords
intotheNEMA5-15Routput
receptacles
A
(PDUMH15NET2)
orNEMA5-15/20Routput
receptacles
A
(PDUMH20NET2).
TheLED
B
near each output
receptacle illuminates when the
receptacleisreadytodistribute
live AC power. The digital load
meter
C
will display the total
connected equipment load in amps.
12-10-311 93-327B.indb 4 12/13/2012 4:09:17 PM