Owner`s manual
i
88
 i P
0 3.0
8 8 8
0 i
0 3.0
0 i
16
Using the Digital Display
Rotating the Display
At any point, pressing both of the arrow 
buttons simultaneously and holding 
for 3 seconds rotates the 2-digit and 
3-digit displays.
Features
Outlets: During normal operation, the outlets 
distribute AC power to connected equipment. 
Outlet Status LED: Once the unit is powered on, each outlet individually 
ramps up and each Outlet Status LED will illuminate when the associated 
outlet is ready to distribute live AC power.
LED Color Outlet Status Comments/Notes
Green On Normal operation. 
Yellow On Outlet current has exceeded 80% of the outlet  
current rating. 
Red Off Outlet voltage is below the Low Voltage threshold.
Flashing Red Off Circuit breaker for this bank has tripped. 
Off Off Outlet is powered off.
Note: Colors noted here reflect standard LED configuration. See chart on page 15 
for full LED color definitions.
C13 C19
Circuit Breaker: There are 6 Load Banks, each protected by a circuit 
breaker. If the connected equipment load exceeds the Maximum Load 
Rating for that bank of the PDU, the circuit breaker will trip. Disconnect 
excess load and reset the breaker.
Note: Each breaker comes equipped with a push-to-reset guard to prevent 
accidental breaker tripping. To turn off the breaker, insert a flathead screwdriver into 
the reset slot.
Mounting Brackets: Use these brackets to mount the PDU.
Mounting Buttons: Come pre-installed on the back side of the PDU and 
are used for toolless mounting. Note: Four additional mounting buttons 
are included for alternate rack styles. 
Outlet Status LED
Push-to-Reset Guard
13-09-017-9332B8.indb 16 9/5/2013 4:26:58 PM