User`s guide
81
4. Telnet/SSH Console continued
4.4.1 Alarms
This menu provides a summary of all alarm conditions, where they have occurred and whether they have been acknowledged.
Alarm Summary
-------- Alarm List ------------------------------------------------------------
Auto Acknowledge Alarms: Off
# Device Alarm Detail ACT ACK
--- ------ --------------------- ------ ------
1 2 Temperature Beyond Limits No No
2 2 Humidity Beyond Limits No No
3 1 Output Off No No
4 1 Battery Age Above Threshold No No
5 2 Temperature Beyond Limits No No
6 2 Humidity Beyond Limits No No
7 1 Output Off No No
8 1 Battery Age Above Threshold No No
9 2 Temperature Beyond Limits No No
10 2 Humidity Beyond Limits No No
11 1 Output Off No No
12 1 Battery Age Above Threshold No No
13 2 Temperature Beyond Limits Yes No
14 2 Humidity Beyond Limits Yes No
15 1 Output Off Yes No
16 1 Battery Age Above Threshold Yes No
#- Alarm Id
A- Acknowledge All Alarms
E- Enable Alarm Auto Acknowledgement
X/M- Return to Main Menu
<ENTER> Refresh Menu
Menu Data
Auto-Acknowledge Alarms
This is a system-wide setting that will automatically acknowledge every alarm on the system. This will force alarm entries to be removed as soon as
the alarm condition clears. This setting should be enabled if using with PowerAlert Network Management System (PAMS) or the PowerAlert Shut-
down Agent (PANSA).
Acknowledge All Alarms
This option gives the user the ability to acknowledge all of the active alarms. Any inactive, unacknowledged alarms will be deleted when this is
done. The alarms acknowledged will be marked as such and as when the alarm condition clears, it will be removed.
4.4 Alarms and Logging
This menu allows for in-depth viewing, configuration and acknowledgement of logs and alarms that come across the system.
Alarms and Logging
-------- Alarms and Logging ----------------------------------------------------
1- Alarms
2- View Logs
3- Logging Settings
X/M- Return to Main Menu