User`s guide
38
4. Telnet/SSH Console continued
4.1 Device Menu continued
4.1.5.3 Ramp/Shed Settings continued
Menu Data
Ramp Action
This is the action to take when a ramp is initiated. The valid values are:
•RemainOff
•TurnOnAfterDelay
Ramp Delay
This is the delay before taking the ramp action.
4.1.6 Preferences and Thresholds
This menu contains the device and protocol specific data that defines the user's preferred behavior settings and thresholds. Since this menu is
used to define the user's preferences, the values here should be editable.
Preferences and Thresholds Menu
-------- Preferences and Thresholds --------------------------------------------
Auto Restart On Shutdown : Enabled
Auto Restart On Delayed W : Enabled
Auto Restart On Low Volta : Enabled
Auto Restart On Overload : Disabled
Auto Restart On Overtemp : Disabled
14 Day Self-Test : Disabled
Watchdog Status : Disabled
Watchdog Time : Disabled
Low Battery Warning : %
Low Battery Warning : 0.0 Years
1- Auto Restart On Shutdown
2- Auto Restart On Delayed Wakeup
3- Auto Restart On Low Voltage
4- Auto Restart On Overload
5- Auto Restart On Overtemp
6- 14 Day Self-Test
7- Low Battery Warning
8- Battery Age Alarm Threshold
X- Device Main Menu
M- Return to Main Menu
<ENTER> Refresh Menu
Shed Action
This is the action to take when a shed is initiated. The valid values are:
•RemainOn
•TurnOffAfterDelay
Shed Delay
This is the delay before taking the shed action.