User`s guide

G H I
3
Figure 2-2: UPS System Shutdown Settings
2. Installation and Configuration continued
6. Click the Action field
F
to access its submenu. Select the device to
shut down in the Select Trigger Device section
G
.
7. Set how long the delay should be before the action will take place
H
.
8. Select the Event(s) that will trigger the action
I
.
9. Click the button on the bottom of the screen
J
.
Note: Whenever changes are made, the button must be pressed
to submit the changes before moving off of the page. This also includes
deleting fields using the button. After selecting an item and clicking
the button press the button to commit the change.
Setting Default Value Additional Information
IP address
Obtain from DHCP
Section 3.8.1
Telnet Access
Enabled
Section 3.8.1
SSH Access
Enabled
Section 3.8.1
HTTP Access
Enabled
Section 3.8.1
HTTP Access
Enabled
Section 3.8.1
SNMPv1 Access
Enabled—Read-Only Community—public
Section 3.8.2
SNMPv2 Access
Enabled—Read-Write Community—tripplite
Section 3.8.2
SNMPv3 Access
Enabled
localadmin
localmanager
localguest
See table below
Section 3.8.2
Default users and passwords
localadmin/localadmin
localmanager/localmanger
localguest/localguest
Section 3.8.2
Radius
Disabled
Section 3.8.2
Email Notication
Default email action profile setup to trigger 30 seconds after an alarm. Add email destinations to
the address book.
Section 3.6
SNMP Trap Notication
Default SNMP Trap action profile setup to trigger 30 seconds after an alarm. Add trap destinations
to the address book.
Section 3.6
Event Logging
Enabled
Section 3.7
Data Logging
Enabled
Section 3.7
2.3 Other Default Settings
SNMPWEBCARD allows a compatible Tripp Lite device to function as an SNMP-managed device on your network, using the SNMP agent and
Management Information Base (MIB). The SNMP agent resides in the SNMPWEBCARD firmware and responds to standard SNMP commands (Get,
Get Next and Set). It can also generate SNMP traps (messages). The MIB determines which parameters can be monitored and controlled. Two MIB
filesTripplite.mib and RFC1628.mibmust be loaded on each Network Management Station that will monitor the managed device. (The files
are provided on the CD-ROM included with the SNMPWEBCARD or network-enabled Tripp Lite device. Consult your Network Management Station
software documentation for instructions on how to import MIB files.)
User Name The identifier of the user profile. SNMP version 3 maps Gets, Sets and Traps to a user profile by matching the user name
of the profile to the user name in the data packet being transmitted. A user name can have up to 32 ASCII characters.
Authentication Passphrase A phrase of 8 to 32 ASCII characters that verifies that the Network Management System (NMS) communicating
with this device through SNMPv3 is the NMS it claims to be, that the message has not been changed during
transmission, and that the message was communicated in a timely manner, indicating that it was not delayed and
that it was not copied and sent again later at an inappropriate time.
Privacy Passphrase A phrase of 8 to 32 ASCII characters that ensures the privacy of the data (by means of encryption) that a Network
Management System (NMS) is sending to this device or receiving from this device through SNMPv3.
Authentication Protocol The Tripp Lite implementation of SNMPv3 supports only MD5 authentication.
Privacy Protocol The Tripp Lite implementation of SNMPv3 supports only DES as the protocol for encrypting and decrypting data.
Public Value A field provided to enter a username/password hint for SNMPv3 Admin users. This SNMPv3 value is part of the SNMPv3
USM User Table.
SNMPv3 Denitions
2.4 SNMP Configuration