Datasheet
Output Capacity Details 8.6kW total; 13.8A per bank input (balanced)
Frequency compatibility 60 Hz
Output nominal voltage 208V: C13 and C19 outlets / 120V: NEMA 5-15/20R outlets
Overload protection 3 20A double-pole circuit breakers (1 per output phase)
Outlet quantity / type 48 total - 36 C13, 6 C19, 6 NEMA 5-15/20R
Outlet Type IEC-C13, IEC-C19, NEMA 5-15/20R
INPUT
Nominal Input Voltage(s)
Supported
208V AC
PDU Input Voltage 208
Maximum Input Amps (A) 24
PDU Plug Type NEMA L21-30P
Input cord length (ft.) 6
Input cord length (m) 1.83
Voltage compatibility
(VAC)
208; 3-Phase
Phase 3-Phase
PHYSICAL
Shipping weight (lbs) 14.5
Shipping weight (kg) 6.6
Unit Dimensions (HWD/in) 70 x 2.65 x 2.2
Unit Dimensions
(HWD/cm)
177.8 x 6.7 x 5.6
Shipping Dimensions
(HWD/in)
76.8 x 9.5 x 5.3
Shipping Dimensions
(HWD/cm)
195.1 x 24.11 x 13.5
Unit weight (lbs) 13.9
Unit weight (kg) 6.3
Material of construction Steel
Style Vertical rackmount
Form factors supported Vertical rackmount installation supported with included mounting brackets; supports toolless mounting in
button-mount compatible racks
PDU Form Factor Vertical (0U)
ENVIRONMENTAL
Relative Humidity 0-95% non-condensing
CERTIFICATIONS
Certifications Tested to UL60950-1 (USA, Canada), NOM (Mexico), Class A (Emissions), ROHS
WARRANTY