Specification Sheet
Specifications
Versatile Installation Options
Mounts horizontally in 1U of EIA-standard 19 in. 2- and 4-post racks
●
Reversible all-metal housing faces front or rear in rack
●
Ready for toolless 0U vertical installation with optional PDUSIDEBRKT (sold separately)
●
Also mounts on wall, workbench or under a counter
●
MODEL TEXT
Key Benefit Delivers 100–240V single-phase AC power to multiple loads from a utility outlet, generator or UPS system in a high-
density IT environment. Ideal for networking, telecom, security, audio/video and sound reinforcement applications.
OVERVIEW
PDU Type Basic
OUTPUT
Output Capacity Details 3.84kW (240V), 3.68kW (230V), 3.52kW (220V), 3.33kW (208V), 3.2kW (200V), 2.03kW (127V), 1.92kW (120V),
1.6kW (100V) / 16A total capacity; 16A max per C19 outlet; 12A (10A CE) max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (12) C13; (2) C19
Output Nominal Voltage 100-240V nominal, single phase
Overload Protection 16A circuit breaker
INPUT
PDU Input Voltage 100; 120; 127; 200; 208; 220; 230; 240
Recommended Electrical Service 20A 120V; 20A 208/240V; 16A 230V
Maximum Input Amps 16
PDU Plug Type IEC-320 C20
Input Cord Details C20 inlet accepts user supplied input cable with C19 output connection
Input Phase Single-Phase
USER INTERFACE, ALERTS & CONTROLS
Switches No power switch
PHYSICAL
Minimum Required Rack Depth
(inches)
7.8
2 / 3