Output Voltage Regulation (Line
Mode)
-10%, +6%
Output Voltage Regulation (Battery
Mode)
+/- 5%
Output Receptacles (10) 5-15R
UPS Output Receptacles (Surge
Suppression Only)
5 UPS outlets, 5 surge-only outlets
Hot-Swap PDU options PDUB15 (2U / 8 5-15R outlets)
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery
Mode)
PWM sine wave
INPUT
Rated input current (Maximum Load) 12A
Nominal Input Voltage(s) Supported 120V AC
UPS Input Connection Type 5-15P
Input Circuit Breakers 15A
UPS Input Cord Length (ft.) 6
UPS Input Cord Length (m) 1.8
Recommended Electrical Service 15A 120V
Input Phase Single-Phase
BATTERY
Half Load Runtime (min.) 7.5 minutes (405 watts)
DC System Voltage (VDC) 24
Battery Recharge Rate (Included
Batteries)
Less than 8 hours from 10% to 90%
Internal UPS Replacement Battery
Cartridge
&nbsp;<a class="productLink" href="//www.tripplite.com/UPS-Replacement-Battery-Cartridge-Tripp-Lite-APC-Belkin-
Best-Powerware-Liebert-other-UPS~RBC51">RBC51</a>&nbsp;(requires 2)
Expandable Runtime No
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 92 to 150
Overvoltage Correction Input voltages between 129 and 147 are reduced by 15%
Undervoltage Correction Input voltages between 92 and 108 are boosted by 18%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display LCD screen with scroll buttons indicates Input voltage, Output voltage, Frequency (Hz), AVR boost / cut status,
Output load in watts, Output load percentage, Battery voltage and Estimated runtime in minutes
Switches Power switch offers whole UPS power control; Scroll/mute button enables LCD selection options and silences
audible alarm; Test button initiates self test