Specification

Specifications
NEMA 5-15P input plug; 6ft / 1.8m line cord
Maintains operation of connected equipment to prevent data loss, equipment damage and downtime
associated with power failures and severe voltage fluctuations
Line Interactive Automatic Voltage Regulation / AVR circuits continuously correct brownouts and
overvoltages from 92 to 150V without using battery power
Network-grade AC surge suppression protects equipment from damage and performance problems
resulting from transient surges
Offers 7.5 minutes runtime 50% load (405 watts)
Supports an entry level desktop system with LCD screen for up to 55 minutes during power failures (75
watts)
LCD display continuously reports operating mode and battery charge level, plus additional UPS and site
power data, such as input & output voltage, frequency, load percentage, load watts, battery voltage and
estimated runtime in minutes
USB port enables data-saving unattended shutdown when used with Tripp Lite's PowerAlert software,
available via FREE download from www.tripplite.com/poweralert
HID-compliant USB interface also enables automatic integration with built-in power management and
auto shutdown features of Windows and Mac OSX
Built-in data line surge suppression offers protection for equipment with single-line dialup or network
ethernet connection, plus one set of coax jacks for CATV / broadcast line protection
Meets strict ENERGY STAR efficiency guidelines
Optional PDUB15 bypass PDU enables hot-swappable UPS replacement with no disruption to
connected equipment
OVERVIEW
UPC Code 037332173249
OUTPUT
Output Volt Amp Capacity (VA) 1500
Output kVA Capacity (kVA) 1.5
Output Watt Capacity (Watts) 810
Nominal Output Voltage(s)
Supported
110V; 115V; 120V
Nominal Voltage Details 120v nominal output in battery mode
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Automatic frequency selection
2 / 5