3. Battery Cabinet Installation (continued)
3.10 Daisy-Chaining Multiple Battery Cabinets
Additional battery strings can be daisy-chained to the UPS internal battery system via a unique connector inside the UPS battery
compartment (Figure 3.10a).
A 15-ft. BP240EXTNDR15DL cable is required to connect the first battery cabinet to the UPS system (Figure 3.10b). Cabling for all
additional built-to-order cabinet installations is the sole responsibility of the electrician performing the installation.
To connect the cable to the UPS, remove the cover plate (Figure
3.10c) and insert the Delta connector into the slot until it is
seated firmly. After removing the cover plate, run the ring terminal
ends through the opening and connect to the breaker (see
Section 6.2). Make sure to use the correct electrician-provided
strain relief at the cover plate.
WARNING: When connecting to the breaker, make sure that
youu maintain proper polarity (positive to positive, etc.).
Failure to do so may result in damage to your UPS and will
void your warranty claim.
Battery
Connection
Battery
Connection
Front of
Cabinet
Conduit
Knockouts