Owner`s manual

13
6. Diagrams (continued)
6.3 Integrated Battery Charger (Select Models)
Notes:
• All dimensions are in inches.
• AC input is preset with fuses for 120V 30 A, but can be rewired for 208 and 240 VAC, 60 Hz by a qualified electrician.
• Constant voltage output.
• Electronic current limiting and high voltage shutdown.
• Temperature compensation with remote battery temperature sensor.
• Auxiliary output circuit for “Charger OK” indicator.
AC
0.5
12.5
13.5
6.25
MAX
Input
WARNING: Do not connect the battery charger
AC input to the UPS system output. The battery
charger requires a separate AC supply circuit.
L N
120 VAC
Output
– +
Output
Input Voltage Selection
For 120 VAC Jumper:
2 & 3, 3 & 4, 5 & 6
For 208 VAC Jumper:
1 & 2, 4 & 5
For 240 VAC Jumper:
2 & 3, 4 & 5